2005 Supreme(Bom) 141
IN THE HIGH COURT OF BOMBAY
MUNICIPAL CORPORATION FOR GREATER BOMBAY
Versus
SHARDA DYEING, PRINTING WORKS
Decided on : FEBRUARY 4, 2005
Subject
Electricity - Metering and Billing
Act Referred
Headnote
D. Y. CHANDRACHUD, J.
( 1 ) THE first respondent is a consumer of the bombay Electric Supply and Transport Undertaking and carries on the business of dyeing and printing. The first respondent has derived electric supply through three meters situated at the premises of the factory. Meter D-833723 was being used for commercial purposes while Meters 0273715 and 0442967 were being used for industrial purposes. The consumption pattern on Meter 0442967 showed that there was a sudden and considerable drop in consumption from 3rd May, 1994. The meter was checked by the Deputy Engineer in the Energy Audit department of the petitioner on 7th December, 1995 in the presence of a representative of the first respondent. On being checked, it was found that the meter was under-recording the consumption of electricity by 65. 76% due to the secondary Circuit of the Current Transformer being open on the red and yellow phases and because of a loose potential connection on the red and yellow phases. According to the petitioner, in ordinary parlance what this meant was that the wires connecting the current transformer and the meter of the red phase and yellow phase were open, as a result of which , the supply through the red and yellow phases was not fed to the meter which was recording the consumption of the consumer. Hence, according to the petitioner, though the supply was being used by the first respondent as usual, due to the loose connection in wiring, the consumption which was recorded in the meter was l/3rd of the actual and hence 2/3rd of the supply was not recorded. On this aspect of the matter, parties, it is evident, are ad idem. In paragraph 6 of the Writ Petition filed by B. E. S. T. Undertaking there is the following averment in regard to the cause for the under- recording of the electricity consumption to the extent of 65. 76%. :"on the said meter being checked it was found that the said meter was under recording consumption by 65. 76 per cent due to the C. T. Secondary Circuit being open on the Red and Yellow Phase and due to loose potential connection on the Red and Yellow Phase. In ordinary parlance, what it really means is that the wire connecting the current transformer and the meter of the Red Phase and Yellow Phase were open. As a result of which the supply through Red Phase and Yellow Phase respectively were not been ted to the meter which records the consumption of the consumer. Thus even though the supply was being used by the 1st respondent as usual, due to the above disconnection in wiring, the consumption recorded on the meter was only one third and hence two third of the consumption of supply was not recorded on the meter. "insofar as this averment is concerned, there is an admission in the following terms in para 9 of the affidavit in reply. "it is true that due to the defect in the connection of Current Transformer (C. T.) and Meter of Red Phase and Yellow Phase, the Meter was not giving proper reading. "
( 2 ) AT this stage, it would be worthwhile to advert to the working of a C. T. operated meter. In meters through which supply for loads upto 100 Amps is derived, the electricity supplied to the consumer passes through the meter itself and is recorded by the meter. However, for consumption with higher installed loads, it is not possible for the entire current consumed to pass through the meter as that would require a meter of an extremely large size. Thus, the meter is connected parallel to the main supply line of the consumer. A current transformer is installed for each phase supplied to the consumer (red, yellow and blue phases) which allows a proportionately small quantity of electricity to pass through the meter, which is then recorded by the meter. The meter thus has a multiplier factor by which the actual recording by a meter is required to be multiplied in order to record actual electricity consumed. For instance, if a meter has a multiplier factor of 20 and the meter indicates 1000 units as having been